BPXBL - 41-60 LEAD ACID BATTERY

  • MSDS: BPXBL
  • Manufacturer: YUASA EXIDE CORP
  • Product Name: 41-60 LEAD ACID BATTERY
  • National Stock Number: 6140-01-333-6738
Product Identification

Product ID:41-60 LEAD ACID BATTERY
MSDS Date:09/01/1993
FSC:6140
NIIN:01-333-6738
MSDS Number: BPXBL

Responsible Party
YUASA-EXIDE CORP
645 PENN ST
READING, PA 19612-4205
US

Emergency Phone: 215-378-0757(800-424-9300 CHEMTREC)

Info Phone: 215-378-0757

Cage: KO888

Contractor
YUASA-EXIDE CORP
READING (FORMALLY IN HORSHAM), PA 19612-4205 US

Telephone: 610-378-0550/ FAX -0616

Cage: KO888

Ingredients

LEAD (SARA 313) (CERCLA)

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: 60%

OSHA PEL SEE 1910.1025

ACGIH TLV: 0.05MG/M3, A3; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


ANTIMONY (SARA 313) (CERCLA)

CAS: 7440-36-0

RTECS: CC4025000

Fraction By Weight: 2%

OSHA PEL 0.5 MG/M3

ACGIH TLV: 0.5 MG (SB)/M3; 9596

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


ARSENIC (SARA 313) (CERCLA)

CAS: 7440-38-2

RTECS: CG0525000

Fraction By Weight: 0.2%

OSHA PEL SEE 1910.1018

ACGIH TLV: 0.01 MG/M3, A1; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


CALCIUM, METAL

CAS: 7440-70-2

RTECS: EV8040000

Fraction By Weight: 0.2%


TIN

CAS: 7440-31-5

RTECS: XP7320000

Fraction By Weight: 0.2%

OSHA PEL 2 MG/M3

ACGIH TLV: 2 MG/M3; 9596


SULFURIC ACID (SARA 302/313) (CERCLA)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 10-30%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3/3 STEL; 9596

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


POLYPROPYLENE

CAS: 9003-07-0

RTECS: TR5000000

Fraction By Weight: 5-10%


POLYSTYRENE

CAS: 9003-53-6

RTECS: WL6475000

Fraction By Weight: 5-10%


STYRENE ACRYLONITRILE

CAS: 9003-54-7

Fraction By Weight: 5-10%


ACRYLONITRILE BUTADIENE STYRENE

CAS: 9003-56-9

Fraction By Weight: 5-10%


STYRENE POLYMER WITH 1,3-BUTADIENE

CAS: 9003-55-8

RTECS: WL6478000

Fraction By Weight: 5-10%


POLYVINYL CHLORIDE RESIN

CAS: 9002-86-2

Fraction By Weight: 5-10%

Hazards

LD50 LC50 Mixture:LD50 (ORAL RAT) IS 2140 MG/KG (H2SO4)
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:NO
Health Hazards Acute and Chronic:ACUTE: MAY CAUSE IRRITATION OF
RESPIRATORY TRACT, EYES, SKIN OR GI TRACT. MAY CAUSE BURNS OF SKIN,
EYES, OR GI TRACT. MAY CAUSE CORNEAL DAMAGE OR BLINDNESS. CHRONIC:
TOOTH EROSION, INFLAMMATION OF NOS E, THROAT AND BRONCHIAL TUBES.
Explanation of Carcinogenicity:THE ELECTROLYTE IS NOT LISTED BY IARC,
NTP, OR OSHA AS A CARCINOGEN. IARC LISTS LEAD AS A CLASS 2B
POSSIBLE CARCINOGEN.
Effects of Overexposure:INHALATION: BURNING SENSATION IN NOSE, THROAT
AND LUNGS, COUGHING, WHEEZING, SHORTNESS OF BREATH. EYES: REDNESS,
TEARING, BLURRED VISION, BURNS, SEVERE PAIN. SKIN: SEVERE PAIN,
BURNS, REDNESS, RASH, I TCHING. INGESTION: BURNS OF MOUTH, THROAT,
AND ESOPHAGUS, SEVERE STOMACH PAIN, NAUSEA, VOMITING.
Medical Cond Aggravated by Exposure:PERSONS WITH A HISTORY OF AILMENTS
OR WITH A PRE-EXISTING DISEASE INVOLVING THE RESPIRATORY TRACT OR
TEETH MAY BE AT INCREASED RISK FROM EXPOSURE.

First Aid

First Aid:INHALATION:REMOVE TO FRESH AIR. RESUSCITATE IF NOT BREATHING.
GET MEDICAL ATTENTION. EYES:IMMEDIATELY FLUSH WITH PLENTY OF WATER
FOR 15 MINUTES HOLDING EYELIDS OPEN. GET PROMPT MEDICAL ATTENTION.
SKIN :REMOVE CONTAMINATED CLOTHING. WASH WITH PLENTY OF WATER FOR
15 MINUTES. GET MEDICAL ADVICE. INGESTION:DO NOT INDUCE VOMITING.
GIVE NOTHING BY MOUTH IF UNCONSCIOUS. GET IMMEDIATE MEDICAL
ATTENTION.

Fire Fighting

Lower Limits:4% (H2)
Upper Limits:74.2% (H2)
Extinguishing Media:USE DRY CHEMICAL, CARBON DIOXIDE, FOAM, HALOGEN.
Fire Fighting Procedures:WEAR FIRE FIGHTING PROTECTIVE EQUIPMENT AND
FULL FACE-PIECE SELF-CONTAINED BREATHING APPARATUS. WATER APPLIED
TO ELECTROLYTE GENERATES HEAT & SPLATTERING.
Unusual Fire/Explosion Hazard:HIGHLY FLAMMABLE HYDROGEN GAS GENERATED
DURING CHARGING & OPERATION OF BATTERIES.

Accidental Release

Spill Release Procedures:SHOULD A BATTERY BREAK OPEN, ISOLATE AREA.
ELECTROLYTE SHOULD BE ABSORBED WITH A NON-ORGANIC TYPE ABSORBENT
SUCH AS DRY SAND OR EARTH. AVOID DILUTION WITH WATER. LEAD SPILLED
FROM THE BATTERY SHOULD B E VACUUMED, DO NOT SWEEP OR USE
COMPRESSED AIR.
Neutralizing Agent:USE SODA ASH OR BAKING SODA TO NEUTRALIZE THE
ELECTROLYTE.

Handling

Handling and Storage Precautions:AVOID THE USE OF UNINSULATED TOOLS. IF
THEY ARE REQUIRED, TAKE CARE NOT TO ELECTRICALLY SHORT THE
TERMINALS. REMOVE METAL JEWELRY BEFORE SERVICING.
Other Precautions:UNDER NORMAL CONDITIONS OF USE, EXPOSURE TO LEAD OR
LEAD CONTAINING COMPOUNDS DOES NOT OCCUR. SHOULD A BATTERY BREAK
OPEN AND A LEAD SPILL OCCUR, PRECAUTIONS SHOULD BE TAKEN TO PREVENT
LEAD DUST FROM BECOMING AIR BORNE.

Exposure Controls

Respiratory Protection:UNDER NORMAL CONDITIONS OF USE, RESPIRATORY
PROTECTION IS NOT REQUIRED. HOWEVER, IF CONDITIONS ARISE THAT
REQUIRE THEIR USE, USE ONLY NIOSH/MSHA RESPIRATORS APPROVED FOR
DUST, FUME AND MIST.
Ventilation:BATTERY CHARGING AREAS MUST BE ADEQUATELY VENTILATED TO
PREVENT HAZARDOUS CONCENTRATIONS OF FLAMMABLE GAS OR ACID MIST.
Protective Gloves:RUBBER GLOVES APPROVED FOR SULFURIC ACID
Eye Protection:CHEMICAL SPLASH GOGGLES AND FACE SHIELD
Other Protective Equipment:EYE WASH STATION AND SAFETY SHOWER.
INDUSTRIAL-TYPE IMPERVIOUS WORK CLOTHING, BOOTS AND APRON AS
REQUIRED.
Work Hygienic Practices:OBSERVE GOOD PERSONAL HYGIENE PRACTICES AND
RECOMMENDED PROCEDURES. LAUNDER CONTAMINATED CLOTHING BEFORE REUSE.
Supplemental Safety and Health
RQ FOR CERCLA AND SARA III IS 1000 LBS (ELECTROLYTE). MSDS WRITTEN FOR
ELECTROLYE- IT IS THE PRIMARY HAZARD DURING NORMAL USE AND
HANDLING. INGREDIENTS FROM A LAUNDRY LIST FROM MFR: POLYPROPYLENE
IS M OST LIKELY INGREDIENT FOR CASE. INGREDIENT 1-5 IS ELECTRODE; 6
IS ELECTROLYTE; REST ARE FOR CASE.

Chemical Properties

HCC:C1
Boiling Pt:B.P. Text:203F,95C
Vapor Pres:10 MM HG
Vapor Density:>1 (AIR=1)
Spec Gravity:>1.23 (WATER=1)
Evaporation Rate & Reference:<1 (N-BUTYL ACETATE=1)
Solubility in Water:COMPLETE (ACID)
Appearance and Odor:NO ODOR. BATTERY CASE IS SEALED. ELECTROLYTE IS
CLEAR OILY LIQUID.

Stability

Stability Indicator/Materials to Avoid:YES
CONTACT OF ELECTROLYTE WITH ORGANIC MATERIAL AND COMBUSTIBLES, STRONG
ALKALIS, REDUCING AGENTS, STRONG OXIDIZING AGENTS
Stability Condition to Avoid:OVERCHARGING, SOURCES OF IGNITION
Hazardous Decomposition Products:SULFURIC ACID MIST, SULFUR DIOXIDE AND
CARBON MONOXIDE MAY BE RELEASED WHEN ELECTROLYTE DECOMPOSES.

Disposal

Waste Disposal Methods:BOTH ELECTROLYTE AND SCRAP BATTERIES ARE
REGULATED HAZARDOUS WASTE. SCRAP BATTERIES CONTAIN MATERIALS WHICH
ARE RECYCLABLE AND MUST BE RETURNED TO AUTHORIZED RECYCLER.
ELECTROLYTE SHOULD BE HAULED TO A PERMITTED TREATMENT FACILITY.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.